Function library – Lenze E82xVxxxKxxxxx User Manual
Page 350
Function library
Free interconnection of digital signals
Free configuration of digital outputs
l
350
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0415
v
(Cont.)
Possible digital signals for C0415
^ 348
20
Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
21
Apparent motor current < current
threshold and output frequency >
Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
22
Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
23
Motor phase failure warning
(DCTRL1−LP1−WARN)
Set C0597 = 2
24
Min. output frequency reached
(f
£ C0010) (PCTRL1−NMIN)
LOW active
25
TRIP error message (DCTRL1−TRIP)
26
Motor is running (DCTRL1−RUN)
27
Motor is running / CW rotation
(DCTRL1−RUN−CW)
28
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
29
Process controller input = process
controller output (PCTRL1−SET=ACT)
30
Reserved
31
Apparent motor current
>
Current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT>ILIM)−RFG−I=0)
Overload monitoring
Apparent motor current = C0054
Current threshold = C0156
32
Digital input X3/E1
Digital inputs
33
Digital input X3/E2
34
Digital input X3/E3
35
Digital input X3/E4
36 (A)
Digital input X3/E5
37 (A)
Digital input X3/E6
38
PTC input X2.2/T1, X2.2/T2
Only connect potential−free
switches to T1/T2!
T1/T2 is active ("HIGH") when the
switch is closed