Dc−bus operation – Lenze E82xVxxxKxxxxx User Manual
Page 469
DC−bus operation
Fuses and cable cross−sections
Mains supply
l
469
EDS82EV903−3.0
9300 vector
Rated fuse current
Cable cross−section
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
Mains 3/PE AC 400/500 V operation with mains choke/mains filter
EVF9321
−
C10
1.5
1.0
EVF9322
−
C10
1.5
1.0
EVF9323
16
C16
2.5
2.5
EVF9324
16
C16
2.5
2.5
EVF9325
20
C20
4.0
2.5
EVF9326
32
C32
−
6.0
1)
EVF9327
80
−
−
25
EVF9328
80
−
−
25
EVF9329
80
−
−
25
EVF9330
160
−
−
70
EVF9331
160
−
−
70
EVF9332
250
−
−
120
EVF9333
250
−
−
120
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2
can be connected to the inverter.
9300 servo
inverter
Rated fuse current
Cable cross−section
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
Mains 3/PE AC 400/500 V operation with mains choke/mains filter
EVS9321
−
C10
1.5
1.0
EVS9322
−
C10
1.5
1.0
EVS9323
16
C16
2.5
2.5
EVS9324
16
C16
2.5
2.5
EVS9325
20
C20
4.0
2.5
EVS9326
32
C32
−
6.0
1)
EVS9327
80
−
−
25
EVS9328
80
−
−
25
EVS9329
80
−
−
25
EVS9330
160
−
−
70
EVS9331
250
−
−
120
EVS9332
250
−
−
120
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2