DC−bus operation

Basic dimensioning
Conditions

12

l

476

EDS82EV903−3.0

12.6

Basic dimensioning

In the following table you will find some basic data to select a drive network. Two examples
show you how to work with the tables.

12.6.1

Conditions

The input powers specified in the tables are only valid if the following requirements for
DC−bus operation are observed:

Basic condition

All feeding points

Connection to the three−phase system only via mains chokes specified.

Mains voltage

U

mains

= 230 V / 50 Hz

U

mains

= 400 V / 50 Hz

Switching frequencies

8200 vector

4 kHz or 8 kHz.

93xx

8 kHz

8200 vector

4 kHz or 8 kHz.

Operating/ambient
temperature

max. +40

_C

Motors
(Three−phase asynchronous
motors, asynchronous servo
motors, synchronous servo
motors)

The DC−bus system must be dimensioned for a simultaneity factor of F

g

= 1

(All motors operate simultaneously with 100 % power in motor mode)