Function library – Lenze E82xVxxxKxxxxx User Manual

Page 394

Advertising
background image

Function library

Code table

10

l

394

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0125
*

v

Baud rate

0

LECOM

System
bus (CAN) 217x

Only for communication modules
on the AIF interface:

l

LECOM−A (RS232) E82ZBL

l

LECOM−A/B/LI 2102

l

System bus (CAN) 217x

Set the baud rate for operation
with system bus function module
E82ZAFCC in C0351.

0

9600 baud

500 kbaud

1

4800 baud

250 kbaud

2

2400 baud

125 kbaud

3

1200 baud

50 kbaud

4

19200 baud

1000 kbaud

C0126
*

v

Behaviour with
communicatio
n error

10

Monitored communication channel

A combination of monitorings is
activated by entering the sum of
the selection values

0

All monitoring deactivated

1

Process data channel of AIF interface

Communication interrupt with
active monitoring trips TRIP CE0

2

Internal communication between
function module on FIF and drive
controller

Communication interrupt with
active monitoring trips TRIP CE5

4

Communication (Bus OFF) for
operation with function module
system bus (CAN) on FIF

Communication interrupt with
active monitoring trips TRIP CE6

8

Remote parameterisation C0370 for
operation with function module
system bus (CAN) on FIF

Communication interrupt with
active monitoring trips TRIP CE7

C0127

v

Setpoint
selection

0

0

Setpoint selection in absolute values in
Hz via C0046 or process data channel
(

±24000 º480 Hz)

1

Scaled setpoint selection via C0141 (0
... 100 %) or process data channel
(

±16384 = C0011)

C0128 Service code

Alterations by Lenze service only!