Function library – Lenze E82xVxxxKxxxxx User Manual

Page 406

Advertising
background image

Function library

Code table

10

l

406

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0310
*

v

Functions for
special
applications 1

0

0

All functions switched off

A combination of functions can be
activated by entering the sum of
the selection values.

1

Behaviour in case of DC−bus
overvoltage

Function active:

Function switched−off:

TRIP "OUE" (Lecom no. 22) in case of
DC−bus overvoltage

Message "OU"

2

Threshold for message "DC−bus
undervoltage (LU)" (400 V
controllers only)

Function active:

Function switched−off:

Threshold = 400 V DC

Threshold = 285 V DC

4

Scaling for I

2

t monitoring

Function active:

Function switched−off:

Scaling to device utilisation (C0056)

Scaling to apparent current
(C0054)

8

Limitation to maximum frequency
(C0011)

Function active:

Function switched−off:

Limitation to maximum frequency
(C0011) inactive
Only use for applications with
parameter set changeover if the
parameter sets have different settings
for C0011!

Limitation to C0011 active

32

Behaviour of power−dependent
switching frequency reduction

Function active:

Function switched−off:

Switching frequency is reduced from
16 kHz to 8 kHz, after 8 kHz operation
for 1 s changeover to 4 kHz.

Switching frequency is
immediately reduced to 4 kHz.

64

Behaviour of the
temperature−dependent
switching frequency reduction
and the process controller output

Function active:

Function switched−off:

l

During operation at a switching
frequency of 16 kHz and if
C0144 = 0, temperature−dependent
switching frequency reduction to 4
kHz is not possible

l

During operation at a
switching frequency of 16 kHz,
reduction to 4 kHz is also
carried out if C0144 = 0

l

During operation with application
I/O, only the process controller
output is reset. The I component is
not reset.

l

During operation with
application I/O, the process
controller output and the I
component are reset.

128

Demagnetising time before the
DC injection brake is activated

Function active:

Function switched−off:

Up to a power of 2.2 kW = 1000 ms
From a power of 3 kW = 250 ms

Up to a power of 2.2 kW = 250 ms
From a power of 3 kW = 1000 ms