Advertising
background image

Mechanical installation

Standard devices in a power range from 3 ... 11 kW

Mounting in "cold plate" technique

5

l

75

EDS82EV903−3.0

5.3.3

Mounting in "cold plate" technique

For this mounting variant you require the controller type E82CV...

The following points are important for safe and reliable operation of the controller:

ƒ

Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at

least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all

specified screw connections.

ƒ

Observe the thermal resistance R

th

given in the table. The values are valid for

controller operation under rated conditions.

Power to be dissipated by the heatsink

Cooling path of heatsink − ambience

8200 vector

P

loss

[W]

R

th

[K/W]

E82CV302K2C

100

£ 0.23

E82CV402K2C

127

£ 0.23

E82CV552K2C

167

£ 0.13

E82CV752K2C

213

£ 0.13

E82CV302K4C

97

£ 0.23

E82CV402K4C

120

£ 0.23

E82CV552K4C

153

£ 0.23

E82CV752K4C

200

£ 0.13

E82CV113K4C

273

£ 0.13

Ambient conditions

ƒ

The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.

ƒ

Temperature at the cooling plate of the drive controller: max. 75 °C.