Mechanical installation – Lenze E82xVxxxKxxxxx User Manual
Page 96
![background image](/manuals/566070/96/background.png)
Mechanical installation
Standard devices in the power range 75 ... 90 kW
Mounting with fixing brackets (standard)
l
96
EDS82EV903−3.0
Controller variant "3xx" (with fully mounted footprint filter)
For this mounting variant you require controller type E82EVxxxK4B3xx.
2
3
1
m
g
³
150 mm
a
b1
k
³
100 mm
c
d1
d2
d
b
l
e
e
f
g
a
L
M 8
max. 15 mm
c1
0
³ 50 mm
³ 50 mm
M 8
18 Nm
159.3 lb-in
8200vec283
Fig. 5−31
Standard mounting with fixing brackets 75 ... 90 kW
Loosen both screws to be able to remove the housing cover. The assembly kit is located under
the housing cover.
Installation of mounting angles
Dimensions
0
Arrange the controllers side by side with spacing to be able to disassemble the eyebolts.
Dimensions [mm]
8200 vector
integr. mains
filter
2)
a
b
b1
c
c1
d
d1
d2
e
1)
g
k
m
E82EV553K4B3xx
E82ZN75334B230
450
802
680
393 28.5 750
38
702
375
11
28
18
E82EV553K4B3xx
E82ZN90334B230
1)
If the function module is attached: observe mounting clearance and cable bending radius. The terminals of function
modules in PT design protrude above the housing by 8 mm.
2)
The integrated mains filters are only designed for controller operation at rated power. Different filters with different
dimensions are possible (
^ 106