Extensions for automation

I/O function module E82ZAFSCO10 (Standard I/O PT)

Technical data

7

l

191

EDS82EV903 EN 3.0

7.4.2

Technical data

Operating conditions

Ambient conditions

Climate

Storage

IEC/EN 60721−3−1

1K3 (−25 to +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 to +70 °C)

Operation

Corresponding to the data of the Lenze standard device used (see documentation
of the standard device).

Pollution

EN 61800−5−1

Degree of pollution 2

Connection data

X3/

Values

62

Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0 … +60 °C)
Carrying capacity I

max

= 2 mA

8

Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0 … +60 °C)
Input resistance

l

R

Input

> 50 k

W (with voltage signal)

l

R

Input

= 250

W (with current signal)

9

Carrying capacity I

max

= 10 mA

7

isolated from terminal X3/39 (GND2)

20

Load capacity:

S I

max

= 40 mA

28

Input resistance: 3.3 k

W

1 = HIGH (+12 … +30 V), PLC level, HTL
0 = LOW (0 … +3 V), PLC level, HTL

E1

1)

E2

1)

E3
E4
39

isolated from terminal X3/7 (GND1)

A1

Load capacity:
I

max

= 10 mA, with internal supply

I

max

= 50 mA, with external supply

1)

Frequency input alternatively 0 … 10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425