Extensions for automation, Terminal data, Connection plan – Lenze E82xVxxxKxxxxx User Manual

Page 199

Advertising
background image

Extensions for automation

I/O function module E82ZAFACO10 (application I/O PT)

Installation

7

l

199

EDS82EV903 EN 3.0

Terminal data

Field

Values

Electrical connection

2−pin plug connector with spring connection

Possible connections

rigid:

1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve
1.5 mm

2

(AWG 16)

Stripping length

9 mm

Connection plan

Controller inhibit (CINH) supply via internal voltage source (X3.3/20)

9

1I 2U

1U

2I

62 63

X3.1

X3.2

+5 V

AIN2

AOUT2

AIN1

AOUT1

1U 9

7

0…+

5V

1k … 10k

A2

A1

7 A4

20 28 E1 E2 E3 E4 E5 E6

X3.3

59

GND

+20 V

DIGOUT2

DFOUT1

DIGOUT1

E82ZAFA016

Controller inhibit (CINH) supply via external voltage source

9

1I 2U

1U

2I

62 63

X3.1

X3.2

+5 V

AIN2

AOUT2

AIN1

AOUT1

1U 9

7

0

+5

V

1k … 10k

A2

A1

7 A4

20 28 E1 E2 E3 E4 E5 E6

X3.3

59

GND

+20 V

+

_

DIGOUT2

DFOUT1

DIGOUT1

24 V ext.

(+12 V DC - 0 % ... +30 V DC + 0 %,

max. 200 mA)

E82ZAFA015

Minimum wiring required for operation

Advertising