Parameter setting

Parameter setting with E82ZBC keypad

Transferring parameters to other standard devices

9

l

229

EDS82EV903 EN 3.0

9.2.5

Transferring parameters to other standard devices

Parameter settings can be easily copied from one standard device to another using the
keypad.

Copy parameter sets from the standard device to the keypad

Step

Key seq.

Result

Action

1.

Connect the keypad to standard
device 1

g
xx.xx

Hz

Function

g is active. The first code in the

user menu (C0517/1, Lenze setting: C0050 =
output frequency) is displayed.

2.

Inhibit controller

s

dc

The drive coasts.

3.

Select C0002 from the user menu

x

f

4.

z

0002

Select C0002

5.

x

i

6.

Select the correct copy function

The settings stored in the keypad are
overwritten.

l

Copy all available parameter sets (PAR1 ... PAR4, if required FPAR1) into the keypad:

– Standard device with function

module application I/O, AS
interface,
INTERBUS, PROFIBUS,
LECOM−B, DeviceNet,
CANopen

z

80

Copy PAR1 ... PAR4 and FPAR1:

ð Set "80"

– Standard device with all other

function modules

z

20

Copy PAR1 ... PAR4:

ð Set "20"

l

Only copy the module−specific parameter set FPAR1 into the keypad:

– Only possible with standard

devices including function
module INTERBUS,
PROFIBUS, LECOM−B,
DeviceNet, CANopen

z

50

Copy FPAR1:

ð Set "50"

7.

Start copying

v

STOre

or

SaUe

The selected parameter sets are copied to the
keypad.
If STOrE or SaUe goes off, the copy process is
complete.

8.

Enable controller

u

The drive operates again.