Function library – Lenze E82xVxxxKxxxxx User Manual

Page 283

Advertising
background image

Function library

Limit value setting

Speed range

10

l

283

EDS82EV903 EN 3.0

C0010

Properties "minimum output frequency":

ƒ

C0010 is approached via the acceleration ramp.

ƒ

C0010 has no effect
– on analog input 2 of the application I/O.
– if the setpoint is selected via frequency input.

ƒ

C0010

³C0011 (from software version 3.5):

– the output frequency is 0 Hz. The drive is at standstill.

ƒ

C0010

³C0011 (software version < 3.5):

– independent of the selected analog setpoint, C0011 is approached via the

acceleration ramp.

– the output frequency is limited to C0011.
– the gain of the analog input must be set to zero (C0027 = 0) to ensure trouble−free

operation.

C0011

Properties "maximum output frequency":

ƒ

When selecting fixed setpoints (JOG), C0011 acts as limitation.

ƒ

C0011 is an internal scaling variable! Therefore major changes may only be carried
out when the controller is inhibited!

(

Stop!

Set 0011 so that the maximum permissible motor speed is not exceeded.
Otherwise the motor may be destroyed.

C0239

Properties "lower frequency limitation":

ƒ

During operation with standard I/O, C0239 is approached without acceleration ramp
(jerk!). During operation with application I/O, an acceleration time can be set for
C0239 in C0236.

ƒ

C0239 = 0.00 Hz only allows for one direction of rotation.

Setting tips

ƒ

In case of output frequencies > 300 Hz, avoid switching frequencies < 8 kHz.

ƒ

The display values in C0010 and C0011 can be related to process variables by means
of C0500 and C0501.