Function library – Lenze E82xVxxxKxxxxx User Manual
Page 402
Function library
Code table
l
402
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0225
(A)
Acceleration
time − process
controller
setpoint
(PCTRL1−SET1)
0.00
0.00
{0.02 s}
1300.00 Ramp function generator for
process controller setpoint =
PCTRL1−RFG2
C0226
(A)
Deceleration
time − process
controller
setpoint
(PCTRL1−SET1)
0.00
0.00
{0.02 s}
1300.00
C0228
(A)
Fade−in time −
process
controller
0.000 0.000
{0.001 s}
32.000 0.000 = process controller output
information is communicated
without being displayed
C0229
(A)
Fade−out time −
process
controller
0.000 0.000
{0.001 s}
32.000 0.000 = fade−out switched off
(C0241)
C0230
(A)
Lower limit for
process
controller
output
−100.0 −200.0
{0.1 %}
200.0 Asymmetrical limitation of the
process controller output, based
on C0011
l
If the value falls below C0230
or exceeds C0231:
– Output signal PCTRL1−LIM =
HIGH after expiration of the
time set in C0233
l
Set C0231 > C0230
C0231
(A)
Upper limit for
process
controller
output
100.0 −200.0
{0.1 %}
200.0
C0232
(A)
Offset for
inverse
characteristic
of process
controller
0.00
−200.0
{0.1 %}
200.0 Based on C0011
C0233
*
(A)
Deceleration
PCTRL1−LIM=
HIGH
0.000 0.000
{0.001 s}
65.000 "Debouncing" of digital output
signal PCTRL1−LIM (limits for
process controller output
exceeded)
l
Sets PCTRL1−LIM = HIGH if the
following still holds true after
expiration of the set time:
– Value fallen below C0230 or
exceeded C0231
l
Transition HIGH
ð LOW
without deceleration
C0234
*
(A)
Deceleration
PCTRL1−SET=
ACT
0.000 0.000
{0.001 s}
65.000 "Debouncing" of digital output
signal PCTRL1−SET=ACT (process
controller setpoint = actual
process controller value)
l
Sets PCTRL1−SET=ACT = HIGH if
the following still holds true
after expiration of the set time:
– Difference between
PCTRL1−SET and PCTRL1−ACT
is within operating threshold
C0235
l
Transition HIGH
ð LOW
without deceleration