Extensions for automation
Standard devices in a power range from 15 ... 90 kW
Mounting and dismounting function modules
l
186
EDS82EV903 EN 3.0
Dismounting
8200vec622
Fig. 7−10
Worksteps
The following worksteps apply to the interfaces FIF I (at the top) and FIF II (at the bottom).
1. Disconnect the drive controller from mains and wait at least 3 minutes!
2. Carefully press the clip
0 upwards and remove the function module 3.
3. Plug the FIF cover
2 to the terminals of the interface.
– Make sure that the pins of the FIF interface are plugged correctly in the sockets of
the FIF cover and are not bent.
– Without the FIF cover, the controller is inhibited.
4. Plug on the blanking cover
1.
5. Push the blanking cover
1 until the clip 0 locks into place.
– If no function module is plugged on, the controller without FIF cover
2 and
blanking cover
1 must not be commissioned (dangerous electrical voltage at the
FIF interface).