Extensions for automation

I/O function module E82ZAFACO10 (application I/O PT)

Installation

7

l

201

EDS82EV903 EN 3.0

Analog input configuration

10

9

8

7

2

1

4

3

6

5

Lenze setting (bold printing in tables)

Ÿ 1 − 3
Ÿ 2 − 4
Ÿ 7 − 9
Ÿ 8 − 10

)

Note!

If a setpoint potentiometer is supplied internally via X3.2/9, the jumper must
be set between 0 ... +5 V. Otherwise it is not possible to use the whole speed
range.

Analog inputs

Possible levels

0 ... +5 V

0 ... +10 V

−10 ... +10 V

X3.1/1U
Analog input 1, AIN1

Jumper

7 − 9: free

7 − 9

7 − 9

Code

C0034/1 = 0

C0034/1 = 0

C0034/1 = 1

X3.1/2U
Analog input 2, AIN2

Jumper

8 − 10: free

8 − 10

8 − 10

Code

C0034/2 = 0

C0034/2 = 0

C0034/2 = 1

Analog inputs

Possible levels

0 ... +20 mA

+4 ... +20 mA

+4 ... +20 mA

1)

X3.1/1I
Analog input 1, AIN1

Jumper

optional

optional

optional

Code

C0034/1 = 2

C0034/1 = 3

C0034/1 = 4

X3.1/2I
Analog input 2, AIN2

Jumper

optional

optional

optional

Code

C0034/2 = 2

C0034/2 = 3

C0034/2 = 4

1)

open−circuit monitored

Analog output configuration

10

9

8

7

2

1

4

3

6

5

Lenze setting (bold printing in tables)

Ÿ 1 − 3
Ÿ 2 − 4
Ÿ 7 − 9
Ÿ 8 − 10

Analog outputs

Possible levels

0 ... +10 V

0 ... +20 mA

+4 ... +20 mA

X3.2/62
Analog output 1,
AOUT1

Jumper

1 − 3

3 − 5

3 − 5

Code

C0424/1 = 0

C0424/1 = 0

C0424/1 = 1

X3.2/63
Analog output 2,
AOUT2

Jumper

2 − 4

4 − 6

4 − 6

Code

C0424/2 = 0

C0424/2 = 0

C0424/2 = 1