Technical data – Lenze E82xVxxxKxxxxx User Manual

Page 34

Advertising
background image

Technical data

Operation with rated power (normal operation)
Rated data for a mains voltage of 230 V

4

l

34

EDS82EV903 EN 3.0

Typical motor power
Three−phase asynchronous
motor (4−pole)

P

rated

[kW]

1.5

2.2

P

rated

[hp]

2.0

3.0

8200 vector type

EMC filter integrated

E82xV152K2C0xx

E82xV222K2C0xx

3)

Without EMC filter

E82xV152K2C2xx

E82xV222K2C2xx

3)

Mains

1/N/PE

3/PE

1/N/PE

3/PE

Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)

without mains choke

I

mains

[A]

15.0

9.1

with mains choke

I

mains

[A]

12.5

6.3

18.0

9.0

Output power +U

DC

, −U

DC

1)

P

DCres

[kW]

1.1

0.4

Rated output
current at
switching
frequency

2 kHz sin

I

r

[A]

7.0

9.5

4 kHz sin

8 kHz sin

I

r

[A]

7.0

9.5 (E82CV...: 8.5)

16 kHz sin

2)

I

r

[A]

4.6

6.2

Max. permissible
output current for
60 s at switching
frequency

2 kHz sin

I

max

[A]

10.5

14.2

4 kHz sin

8 kHz sin

I

max

[A]

10.5

14.2

16 kHz sin

2)

I

max

[A]

6.9

9.3

Power loss (operation with I

N8

)

E82EV...

P

loss

[W]

100

130

E82DV... inside/outside

P

loss

[W]

33/67

43/87

E82CV... inside/cooler

P

loss

[W]

33/67

43/87

Dimensions

Dependent on the mounting variant (

^ 61)

Mass

E82EV...

m [kg]

1.6

E82DV...

m [kg]

1.6

E82CV...

m [kg]

1.1

1)

Power supplied by the DC bus when operating with power−adapted motor

2)

Switching frequency is reduced to 4 kHz if

J reaches max. − 5 °C

3)

Operation only permitted with mains choke (

^ 106)

Advertising