Function library – Lenze E82xVxxxKxxxxx User Manual

Page 395

Advertising
background image

Function library

Code table

10

l

395

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0135

*

Drive controller
control word
(parameter
channel)

Bit

Assignment

l

Control of drive controller via
parameter channel. The most
important control commands
are summarised in bit
commands

l

C0135 cannot be changed
using the keypad

1|0

JOG1, JOG2, JOG3 or C0046
(NSET1−JOG1/3, NSET1−JOG2/3)

00
01
10
11

C0046 active
JOG1 (C0037) active
JOG2 (C0038) active
JOG3 (C0039) active

2

0
1

Current direction of rotation
(DCTRL1−CW/CCW)
Not inverse
Inverse

3

0
1

Quick stop (DCTRL1−QSP)
Not active
Active

4

0
1

Stop ramp function generator
(NSET1−RFG1−STOP)
Not active
Active

5

0
1

Ramp function generator input = 0
(NSET1−RFG1−0)
Not active
Active (deceleration at C0013)

RFG1 = ramp−function generator
main setpoint

6

0
1

UP function motor potentiometer
(MPOT1−UP)
Not active
Active

7

0
1

DOWN function motor potentiometer
(MPOT1−DOWN)
Not active
Active

8

reserved

9

0
1

Controller inhibit (DCTRL1−CINH)
Controller released
Controller inhibited

10

TRIP set (DCTRL1−TRIP−SET)

Sets "external error" fault in the
drive controller (EEr , LECOM no.
91)

11

0

Þ 1

TRIP reset (DCTRL1−TRIP−RESET)
Edge causes TRIP reset

13|12

Change over parameter sets
(DCTRL1−PAR2/4, DCTRL1−PAR3/4)

00
01
10
11

PAR1
PAR2
PAR3
PAR4

14

0
1

DC injection brake (MTCRL1−DCB)
Not active
Active

15

Reserved

Advertising