Function library – Lenze E82xVxxxKxxxxx User Manual

Page 258

Advertising
background image

Function library

Operating mode
V/f characteristic control

10

l

258

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0015

uSEr

V/f rated
frequency

50.00 7.50

{0.02

Hz}

960.00

l

C0015 is calculated and saved
during the motor parameter
identification with C0148.

l

The setting applies to all
permitted mains voltages

^ 257

^ 261

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

device−dependent

Setting applies to all permitted
mains voltages

^ 257

Set V/f characteristic

Select the V/f characteristic suitable for your application in C0014.

)

Note!

Please observe the following if you operate drives with quadratic V/f
characteristics:

ƒ

Great moments of inertia reduce the acceleration of the drive.

ƒ

This drive behaviour can be avoided if the linear V/f characteristic is used via
parameter set changeover during acceleration.

Set V/f rated frequency

The V/f rated frequency determines the lead of the V/f characteristic and is a crucial factor
for the motor behaviour in terms of current, torque and power.

ƒ

The setting in C0015 applies to all permissible mains voltages.

ƒ

The internal mains voltage compensation compensates for fluctuations in mains
voltage during operation so that these need not be considered when setting C0015.

ƒ

Depending on the setting in C0015, the maximum output frequency (C0011) may
have to be adapted to be able to cover the entire speed range.

ƒ

The V/f rated frequency depends on the rated controller voltage, the rated motor
voltage and the rated motor frequency:

C0015 [Hz] + U [V]

U

r

[V] @ f

r

[Hz]

U

400 V for E82xVxxxK4C types

U

230 V for E82xVxxxK2C types

V

r

Rated motor voltage depending on the connection method
according to nameplate data

f

r

Rated motor frequency according to nameplate data

)

Note!

C0015 is calculated during motor parameter identification. The value is saved
automatically.

Advertising