Function library

Thermal motor monitoring
Temperature monitoring of the motor with PTC and earth−fault detection

10

l

360

EDS82EV903 EN 3.0

Activation

)

Note!

ƒ

In the Lenze setting, the temperature monitoring of the motor is switched
off!

ƒ

If you are dealing with several parameter sets, you must activate the
monitoring in each parameter set!

1. Connect the monitoring circuit of the motor to X2/T1 and X2/T2.

– If 1.6 k

W < R < 4 kW the monitoring is activated.

2. Set the reaction of the controller:

– C0119 = 0 or 3: Temperature monitoring of the motor is switched off
– C0119 = 1 or 4: TRIP fault message (keypad display: OH3

a)

– C0119 = 2 or 5: Warning signal (keypad display: OH51

e)

Verification

Connect the PTC input to a fixed resistor:

ƒ

R > 4 k

W: A fault message OH3 or OH51 must be initiated.

ƒ

R < 1 k

W: A fault message must not be initiated.