Electrical installation
Standard devices in a power range from 0.25 ... 2.2 kW
Fuses and cable cross−sections according to UL
l
127
EDS82EV903 EN 3.0
6.4.4
Fuses and cable cross−sections according to UL
Supply conditions
Range
Description
Fuses
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
rms
: All classes are permissible
l
System short−circuit current up to 50000 A
rms
: Only classes "CC", "J", "T" or "R" permissible
Circuit−
breaker
l
Only in accordance with UL 489
l
Manufacturer/type
– ABB: S 200 U Charact. K
– Schneider Electric: Multi9 C60 Charact. C
– Moeller: FAZ−C Charact. C
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!