Function library – Lenze E82xVxxxKxxxxx User Manual

Page 279

Advertising
background image

Function library

Behaviour in the event of mains switching, mains failure or controller inhibit

Controlled deceleration after mains failure/mains disconnection

10

l

279

EDS82EV903 EN 3.0

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0988
*

DC−bus voltage
threshold for
DC−bus voltage
control

0

0
= changeover of
the parameter set
via DC−bus
voltage
deactivated

{1 %}

200

l

It is always changed over
between PAR1 and PAR2

l

Changeover of the parameter
set via terminal, bus or PC is
not possible if C988 > 0!

^ 278

^ 294

Adjustment

Parameter

Code

Setting parameter set 1
(active in case of mains failure)

Setting parameter set 2
(active during normal operation)

Switching threshold

C0988

Set C0988 to approx. 10 % undervoltage:

AC 230 V

ð C0988 = 75 ... 85 %

AC 400 V

ð C0988 = 75 ... 85 %

AC 460 V

ð C0988 = 75 ... 98 %

Terminal configuration

C0410

Link C0410/4 (DCTRL1−QSP) to a digital
input (X3/E1 ... X3/E6).

Set the terminal configuration for
normal operation.

Quick stop (QSP) active during

normal operation

Invert this input via C0411.
(Lenze setting = LOW−active)

The digital input linked to DCTRL1−QSP
in parameter set 1 must also be linked
to DCTRL1−QSP (not inverted).
Interconnect the digital input.

No quick stop (QSP) during

normal operation

Do not interconnect this input.

The digital input linked to DCTRL1−QSP
in parameter set 1 must not be used.

Deceleration time for quick stop
(QSP)

C0105

Without external brake resistor
Select a value which ensures a
controlled deceleration of the motor to
a standstill after mains disconnection:
1. Set the same value as in parameter

set 2.

2. Switch off mains voltage.

– Parameter set 1 is activated.
– Observe whether the controller

reports an "Overvoltage OU"
during the controlled deceleration.

3. Repeat the controlled deceleration

and reduce C0105 until the
controller reports an "OU" in the
process.

4. Increase this value by approx. 20 %

as a final setting.

Set the deceleration time for QSP
required for the application.

With external brake resistor
Select an external brake resistor with
sufficient dimensioning.
1. Set C0105 as in parameter set 2.
2. Reduce C0105 until the desired

deceleration time is reached after
mains disconnection.