7 setpoints via a bus system, Setpoints via a bus system, Function library – Lenze E82xVxxxKxxxxx User Manual

Page 312

Advertising
background image

Function library

Configuration of analog and digital setpoints and actual values
Setpoints via a bus system

10

l

312

EDS82EV903 EN 3.0

Select setpoint with XT EMZ9371BC keypad

You select the setpoint directly in C0140:

1. Select C0140 in the menus.

2. Set setpoint with

y or z.

Drive behaviour when selecting setpoints via keypad

ƒ

If the controller is enabled, the changed setpoint has a direct effect on the drive.

ƒ

If the controller is inhibited, the setpoint is saved. After the controller has been
enabled, the drive accelerates to the value saved last with the adjusted acceleration
or deceleration time.

Setting tips

ƒ

The setpoint via keypad has an effect on setpoint 1 (NSET1−N1) and setpoint 2
(NSET1−N2). If you want to select different setpoints via keypad:
– Separate the linkage of NSET1−N1 and NSET1−N2 with analog input signals

(C0412/1 = 0 and C0412/2 = 0).

– Now you can set NSET1−N1 in C0046 and NSET−N2 in C0044.

ƒ

Set C0140 = 0 if the setpoint is not selected via C0140, otherwise the drive may start
immediately when the controller is enabled.

10.7.7

Setpoints via a bus system

Setpoints or actual values can be preselected for FIF by means of a bus function module or
AIF by means of a bus module.

A detailed description can be found in the documentation for the modules.

Advertising