Function library
Configuration of analog and digital setpoints and actual values
Digital setpoints via frequency input
l
305
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0428
*
(A)
Gain for
frequency
output
(DFOUT1−OUT)
100
0.0
{0.1 %}
1500.0
C0435
*
v
(A)
Automatic
adjustment of
frequency
input
0
0
= inactive
{1}
4096
l
Only required for speed control
with digital feedback via HTL
encoder
l
Calculates the gain C0426,
depending on C0425 and
C0011
l
C0426 is recalculated after
every change in C0011 or
C0425
l
Always enter the number of
increments divided by the
number of motor pole pairs!
– Example: number of encoder
increments = 4096, 4−pole
motor
Þ C0435 = 2048
Activation
1. If you use X3/E1 or X3/E1 and X3/E2 as frequency inputs, you must ensure that the
inputs are not connected to other digital signals:
– These connections must be removed under C0410
– Otherwise the controller will evaluate the digital setpoint signal in a wrong way!
(
¶ 516 ff)
2. Assign the signal source "frequency input" to the required setpoint or actual value
under C0412 (C0412/x = 2).
3. Activation of frequency input with C0410/24 = 1.
)
Note!
ƒ
In addition to the free configuration under C0412 you can also use the fixed
assignment under C0007 and C0005:
ƒ
Use C0007 to link the function with a digital input.
ƒ
Use C005 to select a configuration which evaluates the frequency input.