Function library

Thermal motor monitoring
I

2

t monitoring

10

l

358

EDS82EV903 EN 3.0

Adjustment

1. Calculate C0120. This value corresponds to a motor utilisation of 100 %:

C0120 [%] + I

r

I

N

@ 100 %

I

r

Rated motor current

I

r

Rated controller current at switching frequency 8 kHz

2. If you decrease C0120 on the basis of the value calculated, the monitoring already

responds at a motor utilisation < 100 %.

3. If you increase C0120 on the basis of the value calculated, the monitoring only

responds at a motor utilisation > 100 %.

The controller switches off with error OC6 if the apparent motor current is greater than the
rated motor current for a longer time.

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C0054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C0120 <

I x 100 %

I

r

N

C0120 =

I x 100 %

I

r

N

C0120 >

8200vec523

Fig. 10−16

Tripping characteristic of I

2

t monitoring

f

Output frequency

t

Release time

I

N

Rated controller current at switching frequency 8 kHz

I

r

Rated motor current

C0054

Apparent motor current

Example:

C0120 +

I

r

I

N

@ 100 %

C0054 = 1.5 x rated motor current
The controller switches off at output frequencies f > 40 Hz with error OC6 after
approx. 60 s.

Setting tips

ƒ

To avoid an early response in the case of forced ventilated motors, deactivate the
function, if necessary.

ƒ

The current limits C0022 and C0023 only have an indirect effect on the I

2

t

calculation. However, you can prevent the motor from being actuated at the
maximum possible utilisation by the settings of C0022 and C0023.

)

Note!

If the controller is actuated at an increased rated power, the I

2

t monitoring can

respond if C0120 is set to a smaller value than 100 %.