Extensions for automation

Standard devices in a power range from 0.25 ... 2.2 kW
Mounting and dismounting function modules

7

l

168

EDS82EV903 EN 3.0

Mounting

8200vec601

Fig. 7−1

Worksteps

1. Disconnect the drive controller from mains and wait at least 3 minutes!

2. Remove the FIF cover

0 from the FIF interface.

3. Remove protective cap

1 of the function module 2 and plug function module onto

the FIF interface.

4. Insert the plug connector

3 into the contact strip of the function module until it

snaps in.

Additionally fit the retaining clip so that the module cannot be removed together with the
terminal strips

5 during wiring:

5. Insert the retaining clip

4 into the recess, place it on the function module and latch

it.

6. Wire the function module (see mounting instructions of the function module).

)

Note!

Keep the FIF cover

0 and the protection cover of the function module 1 so that

you can attach them again after you have dismounted the function module.
The controller can only be commissioned if a function module or the FIF cover

0 is plugged on the FIF interface.