Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 113

Advertising
background image

Electrical installation

Notes on project planning

Motor cable

6

l

113

EDS82EV903 EN 3.0

Cable cross−section

)

Note!

The assignment of the cable cross−sections to the ampacity of the motor
cables was carried out under the following conditions:

ƒ

Compliance with IEC/EN 60204−1 with fixed cable laying

ƒ

Compliance with IEC 60354−2−52, table A.52−5 if the cable is used as part of
a trailing cable

ƒ

Laying system C

ƒ

Ambient temperature 45 °C

ƒ

Continuous operation of the motor with rated current I

rated

If the specifications and conditions differ, the user is responsible for using a
motor cable which complies with the requirements of the real conditions.
Deviations may e.g. be:

ƒ

Laws, standards, national and regional regulations

ƒ

Type of application

ƒ

Motor utilisation

ƒ

Ambient and operating conditions

ƒ

Laying system and bundling of cables

ƒ

Cable type

Motor cable

permanently installed

for trailing cable

Cable cross−section

I

M

[A]

I

M

[A]

[mm

2

]

[AWG]

10.0

11.8

1.0

18

13.8

17.3

1.5

16

19.1

23.7

2.5

14

25.5

30.9

4.0

12

32.8

41.0

6.0

10

45.5

55.5

10

8

60.1

75.5

16

6

76.4

92.8

25

4

94.6

115

35

2

114

140

50

1

146

179

70

00

177

217

95

000

205

252

120

0000

)

Note!

Information on the design of the motor cable is provided in the "System cables
and system connectors" manual.