Electrical installation

Standard devices in the power range 15 ... 30 kW
Motor connection

6

l

146

EDS82EV903 EN 3.0

6.6.5

Motor connection

U

V

W

PE

T1

T2

PE

U, V, W,

PE

5 Nm
44 lb-in

M 6

T1

T2

2,5 Nm

22.1 lb-in

g

k

2,5 Nm

22.1 lb-in

2

1

g

f

k

e

PE

PE

M

3~

M

3~

PTC

PE

PES

PE

U

V

W

T1

T2

J>

PES

PES

PES

PES

PES

PES

8200vec285

Fig. 6−19

Motor connection 15 ... 30 kW

Use low−capacitance motor cables! (core/core

£ 140 pF/m, core/shield £ 230 pF/m)

The shorter the motor cable, the better the drive behaviour!
PES

HF shield termination by PE connection through shield clamp.

T1, T2

Terminals of motor temperature monitoring with PTC thermistor or thermal
contact (NC contact).
Lay a separate cable (shielded) to X2/T1 and X2/T2 for motor temperature
monitoring.
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Lay the control and mains cables separately from the motor cable!

Cable cross−sections U, V, W, PE

8200 vector

mm

2

AWG

E82xV153K4B

10

8

СССССССССС

СССССССССС

E82xV223K4B

СССССССССС

СССССССССС

16

6

СССССССССС

СССССССССС

E82xV303K4B

СССССССССС

СССССССССС

25

3