9400 HighLine | Parameter setting & configuration

I/O terminals

Analog inputs

7.2

Analog inputs

The controller has 2 analog inputs that can be used to detect differential voltage signals in

the range of ±10 V, e.g. analog speed setpoint selections or the voltage signals of an

external sensor (temperature, pressure, etc.).

r

Optionally, analog input 1 can also be used to detect current setpoints.

7.2.1

Terminal assignment/electrical data

Terminal

Use

Electrical data

X3/A1-

X3/A1+

Differential voltage input 1

(no bridge between A1R and A1)

Level: -10 V ... +10 V

Resolution: 11 bits + sign

Normalisation: When

C00034

= "0":

±10 V ≡ ±2

30

Conversion rate: 1 kHz

Current input

(bridge between A1R and A1)

Level: -20 mA ... +20 mA

Resolution: 10 bits + sign

Normalisation: When

C00034

= "1":

-20 mA ... -4 mA = -2

30

... 0

+4 mA ... +20 mA = 0 ... 2

30

When

C00034

= "2":

±20 mA ≡ ±2

30

Conversion rate: 1 kHz

X3/A2-

X3/A2+

Differential voltage input 2

Level: -10 V ... +10 V

Resolution: 11 bits + sign

Normalisation: ±10 V ≡ ±2

30

Conversion rate: 1 kHz

A1+

A1-

A1-

A1R

A2+

A2-

X3