9400 HighLine | Parameter setting & configuration

Motor interface

Initial commissioning | Select switching frequency

80

Firmware 1.37 - 09/2006

L

Automatic chopper frequency reduction
Under

C00018

, it is possible to select "variable" chopper frequencies for the controller.

With this selection, the controller reduces the chopper frequency depending on the

setpoint current.

r

Depending on the current, the controller switches down to an assigned chopper

frequency; the modulation mode remains unchanged.

r

The switching thresholds are device-dependent (see 9400 Hardware Manual, chapter

"Rated data").

r

If instead of a variable switching frequency a fixed switching frequency has been

selected in

C00018

, no switching frequency changeover takes place. Due to the

rotating field frequency range of 0...5 Hz only a lower continuous current and

maximum currents can be applied (see 9400 Hardware Manual, chapter "Rated data").

O

Tip!
With the same load profile, a deactivation due to an excessive controller load (I x t)

is more likely with a fixed chopper frequency setting than with a variable setting.