Acceleration has been limited [0x00b8000c, Deceleration has been limited [0x00b8000d, Jerk has been limited [0x00b8000e – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 535: 9400 highline | parameter setting & configuration

Advertising
background image

L

Firmware 1.37 - 09/2006

535

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

Acceleration has been limited [0x00b8000c]

Deceleration has been limited [0x00b8000d]

Jerk has been limited [0x00b8000e]

Position target is outside software limit positions [0x00b8000f]

Response (Lenze setting printed in bold)

Setting:

C02716/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

The requested profile acceleration is higher than the

maximum acceleration set in

C02705

and has been

limited to this acceleration.

• Reduce acceleration of the traversing profile of the

basic function (manual jog, referencing or

positioning).

• Increase maximum acceleration (

C02705

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".

Response (Lenze setting printed in bold)

Setting:

C02716/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

The requested profile deceleration is higher than the

maximum acceleration set in

C02705

and has been

limited to this acceleration.

• Reduce acceleration of the traversing profile of the

basic function (manual jog, referencing or

positioning).

• Increase maximum acceleration (

C02705

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".

Response (Lenze setting printed in bold)

Setting:

C02716/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

The requested S-ramp time is lower than the minimum

S-ramp time set in

C02706

and has been limited to this S-

ramp time.

• Increase S-ramp time of the traversing profile of the

basic function (manual jog, referencing or

positioning).

• Reduce minimum S-ramp time (

C02706

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".

Response (Lenze setting printed in bold)

Setting:

C02716/2

(; Adjustable response)

;

None … System fault ; Fault ; Trouble : Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

It was tried to position to a target outside the software

limit positions.

• Select position target inside the software limit

positions.

• Increase permissible traversing range (change setting

of the software limit positions).

• Deactivate monitoring of the software limit positions

by the basic function "Limiter".