9400 HighLine | Parameter setting & configuration

TAs for positioning tasks

TA "Multi-purpose positioning" | Program flow

13.2.4.8

Control of the sequence table
A LOW/HIGH edge at the digital input DI6 starts the parameterised program flow if the

controller is enabled and no error is pending.

r

The first step set in C03000 of the sequence table is executed.

r

By setting the digital input DI7 to HIGH level, the program flow can be stopped, if

required (break).

r

Parameter setting: Tab Application parameter  Dialog level Overview  L_Sequencer

Note!

In the following cases the program flow is interrupted:
• The controller inhibit is activated.
• Quick stop is activated.
• The drive interface changes to an error status.
If the controller is not inhibited, a shutdown of the drive via the basic function

"Quick stop" is effected.
After the interruption is deactivated again (e.g. because an activated quick stop

has been deactivated again), a renewed LOW/HIGH edge is required at the

digital input DI6 in order that the positioning program can be continued with

the sequence step.

Parameters

Lenze setting

Value Unit

C03000

Starting step

1

C04504

Jump destination

0

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

C03000  First step

C03079/6

DigIn 6  Sequencer start

C03070/1

DigIn 7  Sequencer break

C03070/2

Controller inhibit

or

Quick stop active

or

Error is active.



Sequencer abort

C03070/6

FALSE  Sequencer jump

C03070/7

DigIn 5  Reset program/error status

C03070/8