9400 HighLine | Parameter setting & configuration

Basic drive functions

Brake control | Carry out brake test

230

Firmware 1.37 - 09/2006

L

Sequence
When all conditions mentioned are fulfilled, the brake test can be started by setting the

input BRK_bBrakeTest to TRUE.

[9-20] Sequence of the brake test

Error behaviour

r

When the stop position of the motor axis has changed during the brake test by more

than the permissible angle of rotation set in

C02595

despite the applied brake:

– The brake test is aborted immediately and the controller is inhibited.
– The status "position drift when brake is applied" is displayed at the status output

BRK_dnState via bit 21 and the status "brake error" is displayed via bit 15.

– The output BRK_bError is set to TRUE.

r

By resetting the input BRK_bBrakeTest to FALSE an error can be reset automatically.



Normal behaviour



Error behaviour

n

C02594

: Test torque

o

C02595

: Permissible angle of rotation

CINH = controller inhibit

r

The specified test torque is created via

a ramp generator with an acceleration

time of 1 s and held max. 4 s.
– By this it is tried to rotate the motor

shaft while the brake is applied.

r

By resetting the input BRK_bBrakeTest

to FALSE the brake test can be aborted.

t

Œ

0
1

M

t

j

t

t

BRK_bBrakeTest

CINH

1 s

max. 4 s





t

BRK_bError