9400 HighLine | Parameter setting & configuration

Commissioning

Standard set-up

3.4

Standard set-up

Worksteps
Transfer application and parameter set to the controller:

1. Transfer the application preconfigured in the »Engineer« and the corresponding parameter set to the

memory module of the controller.

2.

Save parameter set

.

(C 57)

For a motor with an electronic nameplate (ENP):

1. Restart controller with connected motor to read out the motor data from the electronic nameplate

(ENP).

• Restart the controller either by switching off and on again the voltage supply or by the device

command "Restart controller" (

C00002

= "11000").

• See chapter

Motor interface Read the motor data out of the controller

(C 66)

2.

Save parameter set

.

(C 57)

For a motor without an electronic nameplate (ENP):

Note:

Here, the motor is operated with the motor and route data detected during the initial commissioning.

In contrast to the operation of a motor with ENP no resolver errors are compensated and a uniform

saturation characteristic is considered only.

• See chapter

Motor interface Initial commissioning

(C 65)

1. If required, detect rotor displacement angle.

Set rotor displacement angle

(C 71)

• Required for synchronous motors of an original equipment manufacturer and Lenze synchronous

motors with Stegmann absolute value encoder.

2.

Save parameter set

.

(C 57)