9400 HighLine | Parameter setting & configuration

Motor interface

Initial commissioning | Display/edit motor data in the »Engineer«

68

Firmware 1.37 - 09/2006

L

Overview of motor data

Parameters

Information

Lenze setting

Value Unit

C00006

Motor control selection

Servo control with synchronous

motor

C00059

Motor - number of pole pairs

-

C00074

Feedforward control of current controller

Deactivated

C00075

Current controller gain

28.66 V/A

C00076

Current controller reset time

1.50 ms

C00077

Field controller gain

165.84 A/Vs

C00078

Field controller reset time

15.1 ms

C00079

Motor - mutual inductance

- mH

C00081

Motor - rated power

1 kW

C00082

Motor - rotor resistance

- Ohm

C00083

Motor - rotor time constant

- MS

C00084

Motor stator resistance

19.8000 Ohm

C00085

Motor stator leakage induct.

30.500 mH

C00087

Rated motor speed

4000 rpm

C00088

Rated motor current

0.9 A

C00089

Rated motor frequency

200 Hz

C00090

Rated motor voltage

245 V

C00091

Motor - cosine phi

1.00

C00092

Motor - magnetising current

- A

C00128/1

Therm. time constant coil

1.0 min

C00128/2

Therm. time constant plates

5.0 min

C00186

ENP: Identified motor type

-

C00187

ENP: Identified serial number

-

C00188

ENP: Status

-

C00577

Field weakening controller gain

0.000 Vs/V

C00578

Field weakening controller reset time

2000.0 ms

C01190

Motor thermal sensor

KTY83-110

C01191/1

Temperature for spec. characteristic

25 °C

C01191/2

Temperature for spec. characteristic

150 °C

C01192/1

Resistor for spec. characteristic

1000 Ohm

C01192/2

Resistor for spec. characteristic

2225 Ohm

Highlighted in grey = display parameter

Note!

If the motor has been selected via the »Engineer« motor catalog or if the motor

data have been adapted offline in the »Engineer«, all motor data must be

transferred to the controller with an established online connection and stored

with mains failure protection in the memory module (

C00002

= "11").