9400 HighLine | Parameter setting & configuration

Parameter reference

Parameter list | C00002

544

Firmware 1.37 - 09/2006

L

C00002

Parameter | Name:

C00002 | Controller commands

Data type: UNSIGNED_32

Index: 24573

d

= 5FFD

h

Controller commands

C00003

shows the status of the last executed controller command.

• Under

C00150

you can query the current status of the device control.

Selection list

(Lenze setting printed in bold)

Information

0 Load Lenze setting

Resets parameters to Lenze setting.

• Only possible when the application has stopped and

the controller is inhibited.

1 Load start parameters

Loads parameters from the memory module.

• Only possible when the application has stopped and

the controller is inhibited.

5 Activate application

Activates the application selected under

C00005

.

• If the application is also started, depends on the auto-

start setting selected.

• Only possible when the application has stopped.

7 Save selected application

Selects the active application as start application.

11 Save start parameters

Saves parameters fail-safe in the memory module.

20 Delete logbook

Deletes all logbook entries.

21 Archive log file

Exports logbook entries to file.

31 Start application
32 Stop application
33 Reset program

Executes a reset

• All variables except for the RETAIN variables are reset

to their initialisation value.

• The situation corresponds to a power failure or

deactivation/activation of the controller (warm start)

while the program is running.

34 Delete program

Executes a reset (original)

• All variables including RETAIN and PERSISTENT

variables are reset to their initialisation value.

• The application program is deleted and the controller

is reset to its original status.

35 Restart program

Executes a reset (warm start)

• All variables except for the PERSISTENT variables are

reset to their initialisation value.

• The situation corresponds to the start of a new

program loaded into the control (cold start).

36 Reset runtime measurement
41 Inhibit controller
42 Enable controller
43 Reset error
45 Activate quick stop

"

Basic functionQuick stop

"

46 Quick stop reset

"

Basic functionQuick stop

"

47 Internal command 47

For Lenze service only

48 Internal command 48

For Lenze service only