9400 HighLine | Parameter setting & configuration

Motor interface

Extended commissioning | Set current setpoint filter

90

Firmware 1.37 - 09/2006

L

5.2.2

Set current setpoint filter

Due to the high dynamic performance or limit frequency of the closed current control loop

mechanical natural frequencies can be activated which may lead to an unstable speed

control loop.
In order to suppress or damp these resonant frequencies, two current setpoint filters are

integrated in the speed control loop of the controller which are switched off in the default

setting but can be parameterised accordingly, if required.

[5-7]

Optional current setpoint filters (filter cascade) in the speed control loop

Since the frequency response of the speed controlled system is only rarely known to such

an extent that the current setpoint filters can be adjusted to the controlled system in the

run-up, the following example describes how to set current the current setpoint filters.

m = Output of the jerk limitation

C00272/1

C00271/1

C00270/1

Frequency [Hz]

Width [Hz]

Depth [dB]

Filter 1

C00272/2

C00271/2

C00270/2

Frequency [Hz]

Width [Hz]

Depth [dB]

Filter 2

m

m*