9400 HighLine | Parameter setting & configuration

Motor interface

Initial commissioning | Set motor parameters

Sequence
If all conditions are met, the impedance of the controlled system is determined for approx.

30 different frequencies. These valued are used to determine the electrical machine

parameters by means of a mathematical procedure.

r

Since the procedure starts with very low frequencies and always considers several

complete periods, the whole process takes approx. 3 minutes.

r

During the procedure, the motor is energised with a current, the r.m.s. value of which

corresponds to the lower of the following two values:

After successful completion...
...the controller is automatically inhibited and the selected motor data are set in the

corresponding codes.

r

For a permanent acceptance of the settings, the parameter set must be saved

(

C00002

= "11").

r

The device command

C00002

= "42" serves to deactivated the controller inhibit

automatically set by the procedure.

If an error occurs
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-

time undervoltage), the procedure is terminated with controller inhibit without changing

the codes for the motor parameters.

or

Note!

During the procedure, the motor should not rotate.
With synchronous machines, this cannot always be ensured. Although the

current flow is produced in the torque-neutral axis, asymmetries in the machine

lead to a rotation of the rotor.
• In such a case, the measurement would be useless and would have to be

repeated.

• As a remedy, we recommend to use a holding brake.
With asynchronous machines, slight rotations might possibly occur. Their

influence on the measurements is, however, not worth mentioning.
• In case of uncertainties, the measurement should be repeated several times

to check if the results for the stator resistance, the leakage inductance of the

stator and the rotor resistance differ widely. This should not be the case.

• The magnetising inductance and the cos(ϕ) values are not that important for

the diagnostics, because they are strongly non-linear.