9400 HighLine | Parameter setting & configuration

Motor interface

Initial commissioning | Optimise current controller

86

Firmware 1.37 - 09/2006

L

7. Enter the percentage Vp values situated on the grid points in

C02853/1...17

:

[5-6]

Grid point values of the determined saturation characteristic

8. Enter the maximum process current ("15 A") in

C00022

.

9. Switch on the correction (

C02859

= "on").

– When the correction of the stator leakage inductance is switched on, the same

current characteristic is to occur irrespective of the current magnitude.

– Since the current controller gain is corrected actively, the step responses may differ

slightly compared to the previous measurements. In this case

C00075

and

C00076

must be optimised one last time.

10. Save parameter set (

C00002

= "11").

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

0

6.25

12.5

18.75

25

31.25

37.5

43.75

50

56.25

62.5

68.75

75

81.25

87.5

93.75

100

Vp [%]

30

40

57.5

65

72.5

80

87.5

95

107

130

50

45

35

0

1

I

max

[%]

Grid point Setting

Grid point Setting

1

C02583/1

= 130 %

10

C02583/10

= 72.5 %

2

C02583/2

= 130 %

11

C02583/11

= 65 %

3

C02583/3

= 130 %

12

C02583/12

= 57.5 %

4

C02583/4

= 130 %

13

C02583/13

= 50 %

5

C02583/5

= 130 %

14

C02583/14

= 45 %

6

C02583/6

= 107 %

15

C02583/15

= 40 %

7

C02583/7

= 95 %

16

C02583/16

= 35 %

8

C02583/8

= 87.5 %

17

C02583/17

= 30 %

9

C02583/9

= 80 %