7 activate application, 8 save selected application, Activate application (c 58) – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 58: Save selected application (c 58)

Advertising
background image

9400 HighLine | Parameter setting & configuration

Drive interface

Controller commands

58

Firmware 1.37 - 09/2006

L

4.6.7

Activate application

If the memory module contains several applications, you can use this controller command

to activate a different application in the controller.

r

After mains switching, the preset application will be loaded into the controller.

r

If after mains switching another application than the one preset by Lenze is to be

loaded, it must be activated first and then the application selection must be

saved.

Save selected application

M

How to activate a different application:

1. Click the icon to stop the current controller program.
2. Select the number of the application to be activated under

C00005

.

3. Execute the controller command "Activate application" with

C00002

= "5".

• The application with the number set in

C00005

is activated. If it is started

immediately depends on the automatic start setting selected in

C02104

.

4.6.8

Save selected application

After mains switching, the controller always loads the preset application, even if a

different application has been active before.
Use the controller command "Save selected application" to select the active application as

presetting, i.e. the memory module will load this application into the controller after every

mains switching.

r

When the controller command is executed, the parameter set is saved automatically.

M

Execute the controller command "Save selected application" with

C00002

= "7" to

select the active application as presetting.

Note!

When the application is activated, the corresponding parameter set 1 is loaded

automatically and parameter settings executed before will get lost unless the

parameter set was saved before!