9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

514

Firmware 1.37 - 09/2006

L

CAN module (MXI1): Faulty NMT master configuration [0x00a00020]

CAN module (MXI1) RPDO1: Telegram not received or faulty [0x00a10000]

CAN module (MXI1) RPDO2: Telegram not received or faulty [0x00a10001]

CAN module (MXI1) RPDO3: Telegram not received or faulty [0x00a10002]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1: A

configuration error has occurred in the network

management of the CAN master.

• Faulty download of an Engineer or PLC Designer

project.

• Invalid CAN master settings according to DS301V402

and DS405 in the Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C13591/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 1

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C13591/2

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 2

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C13591/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 3

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.