Monitoring of the device utilisation

In

C00064

the device utilisation (i x t) is displayed over the last 180 seconds in [%].

r

If the value displayed in

C00064

exceeds the warning threshold set in

C00123

, the fault

message "device utilisation Ixt > C00123" is output and the fault response set in

C00604

occurs (default setting: "Warning").

r

If the value displayed in

C00064

exceeds 100 %, the fault message "device utilisation

Ixt > 100 %" is output and the fault response "Fault" occurs.
– The fault can only be reset if the value displayed in

C00064

is < 95 % again.

4.2.3

Parameter for status display

Parameters

Information

C00003

Controller command status

C00007

Active application

C00150

Status word 1

C00155

Status word 2

C00183

Device state

C02530

Active function state