3 system block "ls_digitalinput, System block "ls_digitalinput, 9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 124: I/o terminals digital inputs, Control

Advertising
background image

9400 HighLine | Parameter setting & configuration

I/O terminals

Digital inputs

124

Firmware 1.37 - 09/2006

L

7.4.3

System block "LS_DigitalInput"

The system block LS_DigitalInput displays the digital inputs and the status of the state bus

in the function block editor.

Output

DIS code | data type

Value/meaning

DIGIN_bCInh

C00443/9

| BOOL

Status signal "Controller inhibit"

• An inverter is used to connect control input RFR (X5/pin 9) for the setting/reset of

controller inhibit to the device control (DCTRL).

TRUE Controller inhibit active

DIGIN_bIn1

C00443/1

| BOOL

...

DIGIN_bIn8

C00443/8

| BOOL

Digital inputs 1 ... 8

DIGIN_bStateBusIn

C00443/12

| BOOL

State bus status

Monitoring function "State bus" (C 127)

TRUE A device connected to the state bus has set the state bus to LOW

level and the status "Error" has been set.

• Status "Error" is also set if a device connected to the state bus is

not supplied with voltage.

LS_DigitalInput

DIGIN_bIn1

DIGIN_bIn2

DIGIN_bIn5

DIGIN_bIn4

DIGIN_bIn3

X5

DIGIN_bIn6

DIGIN_bIn7

DIGIN_bIn8

DIGIN_bCInh

DIGIN_bStateBusIn

1

0

1

C00114/1...8

C00443/1...8

CONTROL

GI

RFR

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

GE

24E

SB

X2

DriveInterface

1