9400 HighLine | Parameter setting & configuration

Parameter reference

Parameter list | C00128

556

Firmware 1.37 - 09/2006

L

C00128

C00129

C00130

C00131

C00132

C00142

Parameter | Name:

C00128 | Therm. motor time constant

Data type: UNSIGNED_32

Index: 24447

d

= 5F7F

h

Setting range

(min. value | unit | max. value)

0.1

min

600.0

Subcodes

Lenze setting

Information

C00128/1

1.0 min

Therm. time constant coil

C00128/2

5.0 min

Therm. time constant plates

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM ; MOT Scaling factor: 10

Parameter | Name:

C00129 | Brake resistance value

Data type: INTEGER_32

Index: 24446

d

= 5F7E

h

Required for monitoring of the brake resistor temperature.
Setting range

(min. value | unit | max. value)

Lenze setting

0

Ohm

500 180 Ohm

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00130 | Max. power of brake resistor

Data type: INTEGER_32

Index: 24445

d

= 5F7D

h

Required for monitoring of the brake resistor temperature.
Setting range

(min. value | unit | max. value)

Lenze setting

0

W

800000 5600 W

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00131 | Therm. capacity of brake resistor

Data type: INTEGER_32

Index: 24444

d

= 5F7C

h

Required for monitoring of the brake resistor temperature.
Setting range

(min. value | unit | max. value)

Lenze setting

0

kWs

1000 485 kWs

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00132 | Max. temp. of brake resistor

Data type: INTEGER_32

Index: 24443

d

= 5F7B

h

When this temperature is reached, the brake resistor will be switched off and switched on again if the temperature

is fallen below with a hysteresis of 5 K.
Setting range

(min. value | unit | max. value)

Lenze setting

0

°C

1000 200 °C

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00142 | Autom. restart after mains ON

Data type: UNSIGNED_32

Index: 24433

d

= 5F71

h

Starting performance of the controller after mains connection or fault
Selection list

(Lenze setting printed in bold)

0 Inhibited
1 Enabled

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT