L

4.6.3

Start/stop application

With an online connection, these controller commands can be executed via the

corresponding toolbar icons of the »Engineers«.

r

Alternatively, the controller commands can also be activated with the parameter

settings listed in the "Controller command" column (e.g. via the keypad).

4.6.4

Load Lenze setting

This controller command resets the parameter settings to the Lenze setting. All parameter

changes get lost.

r

Only possible when the application has stopped and the controller is inhibited.

r

This controller command only affects the settings of the operating system, application

and module parameters, the active application and the configuration selected with the

function block editor remain unchanged.

M

How to load the Lenze setting:

1. Click the icon to stop the current controller program.

2. Click the icon to set the controller inhibit.
3. Execute the controller command "Load Lenze setting" with

C00002

= "0".

Symbol

Function

Controller command

Start application in controller

C00002

= "31"

Stop application in controller

C00002

= "32"

Note!

If the drive is stopped during operation, the drive is braked to standstill via the

basic function "Stop".

Standard stop

(C 148)