CAN module (MXI2) PDO manager: Faulty configuration [0x00b00008]

CAN module (MXI2) SDO server: Faulty configuration [0x00b10000]

CAN module (MXI2) SDO client: Faulty configuration [0x00b20000]

Invalid PLC configuration [0x00b80000]

Positive limit switch has tripped [0x00b80001]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: CAN-PDO

configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indices

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: In the CAN

SDP server a configuration error has occurred.

• Faulty project download.

• Invalid SDO server settings according to DS301V402

in the Engineer or PLC Designer.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: In the CAN

SDP client a configuration error has occurred.

• Faulty project download.

• Invalid SDO client settings according to DS301V402 in

the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

An invalid control configuration has occurred.

Load other application.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The

travel range limit switch

in positive traversing

direction has tripped.

Reset error message and

retract limit switch

.