Basic drive functions

General information | Internal state machine

9.1.2.11

Interrupting/replacing states
An active function state cannot be interrupted or replaced by the activation of another

function state. However, the following exceptions apply:

r

The "Initialisation" state replaces all other states.

r

The "Error" state can replace all other states except "Initialisation".

r

The status "Controller not ready" can replace all other states except "Error" and

"Initialisation".

r

The status "Quick stop active" can replace all other states except "Initialisation", "Error"

and "Controller not ready".

9.1.2.12

Priorities
The function states are assigned to priorities so that, if several basic functions are activated

at the same time, it is always changed to the function state with the highest priority:

Priority

Function state

Executable basic function

1

Initialisation

-

2

Error

-

3

Controller not ready

-

4

Quick stop active

Quick stop (C 152)

5

Manual jog active

Manual jog (C 156)

6

Homing active

Homing (C 164)

7

Positioning active

Positioning (C 176)

8

Setpoint follower (position) active

Position follower (C 183)

9

Setpoint follower (speed) active

Speed follower (C 190)

10

Setpoint follower (torque) active

Torque follower (C 196)

10

Brake check

Brake control (C 211)

12

Drive is stopped

Standard stop (C 148)

1 ≡ highest priority; 1 2≡ lowest priority

Note!

The basic state "Drive in standstill" is accepted automatically if no other state is

active.