9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

464

Firmware 1.37 - 09/2006

L

DC-bus capacitor: Temperature > CXXXXX [0x00770004]

DC-bus capacitor: overtemperature [0x00770005]

Inside the device: Temperature > CXXXXX [0x00770006]

Inside the device: Overtemperature [0x00770007]

CPU: Temperature > C00126 [0x00770008]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked : Warning … Information

Cause

Remedy

Electrolytic capacitor temperature higher than warning

threshold.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Electrolytic capacitor temperature higher than limit

temperature (120 °C).

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked : Warning … Information

Cause

Remedy

Inside temperature higher than warning threshold.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Inside temperature higher than limit temperature (85

°C).

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Response (Lenze setting printed in bold)

Setting:

C00589

(; Adjustable response)

:

None … System fault ; Fault … Trouble … Quick stop by trouble … Warning locked ; Warning … Information

Cause

Remedy

CPU temperature higher than variable limit temperature

(

C00126

).

• Controller ambient temperature too high.

• Dirty fan or ventilation slots.

• Value set under C00126 is too low.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

• Set a higher value under

C00126

.