Diagnostics & error analysis

Error messages of the operating system

MXI1: CAN module missing or incompatible [0x008c0017]

MXI2: CAN module missing or incompatible [0x008c0018]

Connection table in use [0x008c001a]

Internal error (CRC application) [0x008c001d]

Parameter set faulty [0x00900000]

Lenze setting loaded [0x00900001]

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The CANopen communication module in module

receptacle MXI1 is incompatible with the application.

Use communication module supported by the

application.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The CANopen communication module in module

receptacle MXI2 is incompatible with the application.

Use communication module supported by the

application.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning : Information

Cause

Remedy

This application is provided with a connection table

which means that connections can be changed online

without executing a completely new download.

- (Information only)

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The checksum of the application is faulty.

Retransmit the application to the controller.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Parameter set is invalid.

Transfer parameter set from Engineer to the controller

and save with

C00002

="11".

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning : Information

Cause

Remedy

"Lenze setting has been loaded."