L

DI_bImpActive

C02549/8

| BOOL

Status signal "Pulse inhibit set"

TRUE Power stages are switched with high resistance.

DI_bCInhActive

C02549/9

| BOOL

Status signal "Controller inhibit active"

TRUE The controller inhibit is active.

DI_bWarningActive

C02549/10

| BOOL

Status signal "Warning active"

TRUE A warning is active in the controller.

DI_bUVDetected

C02549/11

| BOOL

Status signal "Undervoltage detected"

• The threshold for the monitoring function depends on the setting under

C00173

.

TRUE DC bus undervoltage detected.

DI_bOVDetected

C02549/12

| BOOL

Status signal "Overvoltage detected"

• The threshold for the monitoring function depends on the setting under

C00173

.

TRUE DC bus overvoltage detected.

DI_bMainSupplyOk

C02549/13

| BOOL

Status signal "mains voltage is applied"

TRUE A voltage is applied to the mains voltage inputs L1, L2 and L3.

DI_bReadyToSwitchOn

C02549/14

| BOOL

Status signal "Controller ready to start"

TRUE The controller has completed the initialisation and is in the device

state "Device is ready to switch on".

DI_bOperationEnabled

C02549/15

| BOOL

Status signal "Operation is enabled"

TRUE The controller is in the "operation" device state and the motor

follows its setpoint according to the selected basic drive function or

is at standstill due to stop or quick stop.

DI_dwErrorCode

DWORD

Error number of the current error message

Error messages of the operating system (C 443)

DI_AxisData

Data structure, which contains all required machine constants.

Output

DIS code | Data type

Value/meaning

Advertising