9400 HighLine | Parameter setting & configuration

TAs for interconnection via electrical shaft

Introduction | Speed or angular synchronism?

12.1.4

Speed or angular synchronism?

The decision whether to use a speed or angular synchronism mainly refers to the

TA

"Electronic gearbox"

(C 297)

Angular synchronism
Use the angular synchronism if the material is not able to absorb any force and no

remaining positional variation may be available. Please note that a position controller

always causes additional trouble in a track since disturbances and reference value

variations must be compensated exactly.

Speed synchronism
Use the speed synchronism if the material is able to absorb force which ensures a better

concentricity.

12.1.5

Rail or cascade structure?

Rail structure
All drives obtain the same master value/master angle.

Cascade structure
Each drive obtains its own master value/master angle which is created or merely prepared

through the upstream drive.

12.1.6

Master or actual value transfer?

Master value transmission
The master value transfer results in a much quieter machine running. The mark

corrections, superimposed control functions and disturbances of the drive, however, do

not affect the system.

Actual value transfer
The actual value transfer results in an uneven machine running. Mark corrections,

superimposed control functions and disturbances of the leading drive affect the system.

Note!

For detailed information about the ETHERNET Powerlink, please see the

"Ethernet" Communication Manual.