Basic drive functions

Standard stop | System block "LS_Stop"

9.2.3

System block "LS_Stop"

The LS_Stop system block in the function block editor maps the basic function "Stop".

Outputs

Identifier

DIS code | Data type

Value/meaning

STP_dnState

C02616

| DINT

Status (bit-coded)

• When the basic function is not active, all bits are set to "0".

• Bits which are not listed are not assigned with a status (always "0").

Bit 1 Drive is braked to standstill.

• The internal state machine is in the function state "Drive is

stopped".

Bit 2 Drive is at standstill.

• The internal state machine is in the function state "Drive in

standstill".

Bit 3 Deceleration phase is active.
Bit 5 CCW rotation is active.

STP_bStopActive

C02617

| BOOL

Status output "stop is active"

TRUE The drive is braked to standstill or is at standstill.

• The internal state machine is in the function state "Drive is

stopped" or in the function state "Drive in standstill".

STP_dnState

STP_bStopActive

n

t

LS_Stop

Activate stopping

(internal status machine)